Valve Regulated Lead Acid (VRLA) AGM technology with efficient gas recombination up to 99%.
Supports up to 400A maximum discharge current for emergency backup and industrial standby systems.
Designed specifically for float service standby power applications.
Robust construction suitable for UPS systems, telecom equipment, industrial backup power, and security systems.
Pure lead construction and proprietary elements improve discharge stability and long-term reliability.
Built in accordance with IEC 61056-1/2:2012, UL1973 Listed (MH66728), and UL1989 Recognized (MH14533).
| Parameter | Specification |
|---|---|
| Model | GP12400 |
| Brand | CSB Battery |
| Nominal Voltage | 12V |
| Capacity (20Hr @1.75VPC) | 48.0Ah |
| Capacity (8Hr @1.75VPC) | 43.6Ah |
| Capacity (8Hr @1.80VPC) | 43.0Ah |
| Battery Type | VRLA AGM / Sealed Lead Acid |
| Design Life | Up to 5 Years |
| Max Charge Current | 12.0A |
| Max Discharge Current | 400A |
| Short Circuit Current | 1012A |
| Internal Resistance | Approx. 8.5mΩ |
| Terminal Type | I2 Thread Lead Alloy Terminal (M6 Bolt) |
| Terminal Torque | 5.10±1.0 N·m |
| Weight | 12.92kg (28.48 lbs) |
| Dimensions (L×W×H) | 197.0 × 165.0 × 170.4 mm |
| Container Material | ABS (UL 94-HB) |
| Flame Retardant Option | 94-V0 available upon request |
| Operating Temp (Discharge) | -15°C ~ 50°C |
| Operating Temp (Charge/Storage) | -15°C ~ 40°C |
| Float Charging Voltage | 13.5 – 13.8V |
| Equalization Charging Voltage | 14.4 – 15.0V |
| Self Discharge | Less than 10% after 90 days |